GAP30 Gas Alarm Control Panel
Gas alarm control panel with 128×64 graphic LCD, LEDs and buzzer, 72×144 mm front; operating range -10…50 °C.
The GA10 series gas detector senses natural gas (methane) and LPG leaks in homes and similar premises and gives audible and visual alarms. Its relay output can operate a gas shut-off solenoid valve.
| Detected gases | Natural gas (methane), LPG (liquefied petroleum gas) |
|---|---|
| Device type | Type A (visual alarm, audible alarm and output signal) |
| Visual indication | Green: system active, red: alarm, yellow: fault |
| Sensor type | Semiconductor (5 V ± 0.1) |
| Body material | ABS |
| Warm-up/calibration time | 1.5 minutes |
| Response time | <10 seconds |
| Audible alarm | Piezoelectric buzzer |
| Alarm sound level | 85 dB |
| Operating voltage | 230 VAC 2.5 VA ±10%, 50/60 Hz |
| Relay output | 230 V AC 7 A NO |
| Power consumption | 3 W |
| Detection range | 3-20 LEL (APS) |
| Protection class | IPX2D |
| Area of use | Homes and similar premises |
| Operating temperature | -10 °C ... +50 °C |
| Relative humidity | 0-95% |
| Dimensions | 60 mm x 100 mm x 45 mm |
| Reference standards | EN 50194-1, EN 60335-1, EN 60079-29-1, EN 50244 |
Gas alarm control panel with 128×64 graphic LCD, LEDs and buzzer, 72×144 mm front; operating range -10…50 °C.
Gas alarm device with dry contact output for natural gas and LPG; 3–20 LEL detection, 85 dB audible alarm, 230 V AC 7 A relay.
ATEX gas alarm device with plastic housing for natural gas and LPG; visual and audible alarm (85 dB), 230 V AC 7 A relay output.
ATEX-certified gas detector with metal housing; models A–E for LPG, natural gas, methane, butane, propane and alcohol.